- Example: ß
20
= 75 means “every 75 particles 20 micron ISO dust sent, one passes”.
- Efficiency
ε
xx = YY % : same meaning as Beta-value, but not any ISO standardised test
method, hence sometimes used for particles larger than 25..45 micron.
- Example:
ε
20
= 98,7% means “every 75 particles 20 micron non-ISO dust sent, one passes,
which is 98,7% stopped.”
6.3.2
Fuel heating requirements HFO
Heating is required for:
●
Bunker tanks, settling tanks, day tanks
●
Pipes (trace heating)
●
Separators
●
Fuel feeder/booster units
To enable pumping the temperature of bunker tanks must always be maintained 5...10°C
above the pour point, typically at 40...50°C. The heating coils can be designed for a temperature
of 60°C.
The tank heating capacity is determined by the heat loss from the bunker tank and the desired
temperature increase rate.
DAAB605814
6-11
6. Fuel Oil System
Wärtsilä 46F Product Guide
Summary of Contents for 46F Series
Page 1: ...Wärtsilä 46F PRODUCT GUIDE ...
Page 4: ...This page intentionally left blank ...
Page 8: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 86: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 154: ...This page intentionally left blank ...
Page 162: ...This page intentionally left blank ...
Page 170: ...This page intentionally left blank ...
Page 176: ...This page intentionally left blank ...
Page 194: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 207: ...Fig 21 7 List of symbols DAAF406507 7 DAAB605814 21 5 21 ANNEX Wärtsilä 46F Product Guide ...