WAGO-I/O-SYSTEM 750
Appendix 149
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
Table 45: PROFIsafe F parameters
F Parameters
Default value Description
F_Block_ID
0 / 1
The
F_Block_ID
parameter specifies the
format of the F parameter set. If F_Block_ID
has the value 0, the F_iPar_CRC parameter is
not included in the F parameters and the iPar
server is not used. If F_BLOCK_ID has the
value 1, the F_iPar_CRC parameter is included
in the F parameters and the PROFIsafe I/O
module can use the iPar server.
The PROFIsafe I/O module supports both
formats. To set this parameter, the correct
PROFIsafe I/O module must be selected for
device configuration with the configuration
tool of the safe PLC:
F_Block
_ID
Module designation
0
75x-666 4FDI/2FDO 24V/10A DC
1
75x-666 4FDI/2FDO iPar-Server
F_Par_Version
V2 mode
The
F_Par_Version
parameter specifies the
PROFIsafe version to be used communication.
The PROFIsafe I/O module supports
PROFIsafe V1 mode and PROFIsafe V2 mode
and use the version specified with this
parameter:
F_Par_Version
Version
V1 mode
PROFIsafe V1 mode
V2 mode
PROFIsafe V2 mode
F_Source_Add
2004
The
F_Source_Add
parameter specifies the
PROFIsafe source address. To prevent
incorrect parameterization, the address of the
configuration tool is automatically assigned
and cannot be changed.
The parameter can accept values from 1 to
65534.