WAGO-I/O-SYSTEM 750
Connect Devices
61
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
You can set the
Short circuit test
parameter of both inputs used to "active" or
"not active". Please note that the
Short circuit test
parameter must be set the
same for both digital inputs.
If you connect the digital inputs via the switching elements directly to the field
voltage of _24 V or to two semiconductor outputs of a sensor, then you have to set
the
Short circuit test
parameter to "not active" because otherwise the PROFIsafe
I/O module detects a short circuit and outputs the "Short circuit" diagnostic
message.