42
Device Description
WAGO-I/O-SYSTEM 750
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
4.6.9.2
Typical Response Time of the Digital Inputs in an Error-free Case
Only use response times in the event of a failure for the safety response time!
To prevent any personal injury or property damage, only use the values of the safe
response time for errors for defining the safety response time (see Section "Safe
Response Times for Digital Inputs in the Event of an Error"). Under no
circumstances may you use the response times for the digital inputs during error-
free operation for the design!
The following table lists the typical response times for the digital inputs in error-
free operation.
Table 22: Safe response time of the digital inputs in the error-free operation
Standard operating mode
Rotary table
operating mode
Single-channel
analysis
Valence
evaluation
equivalent
Valence
evaluation
antivalent
Signal
change
0
1 1
0 0
1 1
0 0
1 1
0 0
1 1
0
Input
filter time
0 ms
15 ms
15 ms
15 ms
9 ms
15 ms
9 ms
15 ms
15 ms
0.5 ms
17 ms
17 ms
17 ms 9.5 ms 17 ms 9.5 ms 17 ms
17 ms
1 ms
19 ms
19 ms
19 ms
10 ms
19 ms
10 ms
19 ms
19 ms
2 ms
21 ms
21 ms
21 ms
11 ms
21 ms
11 ms
21 ms
21 ms
3 ms
25 ms
25 ms
25 ms
12 ms
25 ms
12 ms
25 ms
25 ms
5 ms
33 ms
33 ms
33 ms
13 ms
33 ms
13 ms
33 ms
33 ms
10 ms
53 ms
53 ms
53 ms
19 ms
53 ms
19 ms
53 ms
53 ms
20 ms
93 ms
93 ms
93 ms
29 ms
93 ms
29 ms
93 ms
93 ms
50 ms
211 ms 211 ms 211 ms 59 ms 211 ms 59 ms 211 ms 211 ms
100 ms
411 ms 411 ms 411 ms 109 ms 411 ms 109 ms 411 ms 411 ms
200 ms
808 ms 808 ms 808 ms 209 ms 808 ms 209 ms 808 ms 808 ms