116 Commissioning
WAGO-I/O-SYSTEM 750
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
Use the same value for the output tolerance time of output O1 and O2!
If the
Output Configuration
parameter is set to "H-Side/L-Side 1" or "H-Side/H-
Side 1", the values of the Output tolerance time parameter for both outputs O1
and O2 must be set to the same value. This is checked by the PROFIsafe I/O
module during the parameterization procedure and a suggested correction is
indicated by the PROFIsafe I/O module in the WAGO parameterization tool in
case of deviation.
Use the same value for the test pulse duration of output O1 and O2!
If the
Output Configuration
parameter is set to "H-Side/L-Side 1" or "H-Side/H-
Side 1", the values of the Test pulse duration parameter for both outputs O1 and
O2 must be set to the same value. This is checked by the PROFIsafe I/O module
during the parameterization procedure and a suggested correction is indicated by
the PROFIsafe I/O module in the WAGO parameterization tool in case of
deviation.
7.4.5.11 Line Break Detection Parameter
If you set the
Output Configuration
parameter to the value "H-Side/L-Side 1",
then you can set the
Line break detection
parameter to the "active" or "inactive"
value. If you set another output configuration, then you can only set the
Line
break detection
parameter to the value "inactive".
If you have set the
Line break detection
parameter to "active", the supply lines
from digital power outputs O1B and O2A to the loads to be switched are
monitored for line breaks.
If you have set the
Line break detection
parameter to "inactive", then the supply
lines are not monitored for line breaks by the PROFIsafe I/O module.
Line break diagnostics are performed just once every 4 minutes!
Line break detection is performed once every 4 minutes.
Line break detection is only possible if the test pulse duration is set to > 0
mx!
Line break detection is only possible if the test pulse duration of the digital output
concerned is set to a value > 0 ms.