WAGO-I/O-SYSTEM 750
Commissioning 99
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
8.3.2.2 Enable DHCP via WBM (with existing IP address)
In the delivery state of the head station, the dynamic assignment of the IP
address is active by means of "Dynamic Host Configuration Protocol" (DHCP).
However, if DHCP is not active and you do already have access to your fieldbus
node via an IP address, you can enable DHCP via WBM on "TCP/IP" WBM page.
1.
Open the WBM (see chapter: "Configuring via the Web-Based
Management System (WBM)" >> "Open WBM").
2.
Change to the WBM page "TCP / IP".
3.
Activate the “DHCP“ option to assign a new IP address via DHCP.
4.
Confirm the change with the
[SUBMIT]
button.
5.
Select the WBM page "Administration".
6.
Click the
[SOFTWARE RESET]
button to apply the changed setting.
Alternatively, you can restart the fieldbus node.
The fieldbus node then starts with the new IP address assigned via DHCP.
The connection to the browser is interrupted.
7.
If you want to call the WBM again, you must use now the changed IP
address.
8.
In order to use the IP address permanently, select in the WBM on "TCP/IP"
WBM page the option "IP configuration source: static" (see chapter "Apply
IP address permanently (option "static ")").
9.
In order to use the IP address permanently, select on "TCP/IP" WBM page
the option “static" in the field
Source
and apply the settings for “IP
address”, “Subnet mask” and “Gateway” from the currently used settings.
10. Confirm the change with the
[SUBMIT]
button.
11. Click the
[SOFTWARE RESET]
button to apply the changed setting.