54 Device Description
WAGO-I/O-SYSTEM 750
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
4.2.2
Power Jumper Contacts/Field Supply
The controller 750-363/0040-0000 is equipped with 2 self-cleaning power
contacts for transferring of the field-side power supply to down-circuit I/O
modules. These contacts are designed as spring contacts.
Figure 26: Power Jumper Contacts
Table 15: Legend for Figure “Power Jumper Contacts”
Contact
Type
Function
1
Spring contact
Potential feed-in (Uv) for field supply
2
Spring contact
Potential feed-in (0 V) for field supply
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.