198 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
11.2.5.26 Analog Output Point Extended 3 (74
hex
)
The extension of the “Analog Output Point” class enables the exchange of data
from a fieldbus node that contains over 765 analog output points (AOPs). The
instance scope of the “Discrete Output Point Extended 3” class covers AOPs
from 766 to 1020 in the fieldbus node.
Instance 0 (Class Attributes)
Table 162: Analog Output Point Extended 3 (74
hex
) – Class
Attribute ID Access Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
3
Get
Number of
Instances
UINT
Number of Instances
-
Instance 1 ... 255 (Analog output value 766 up to 1020)
Table 163: Analog Output Point Extended 3 (74
hex
) – Instance 766...1020
Attribute ID Access Name
Data type Description
Default
value
1
Set
AopObj_Value ARRAY of
BYTE
Analog Output
-
2
Get
AopObj_Value_
Length
USINT
Length of the output data
AopObj_Value (in byte)
-
Common Services
Table 164: Analog Output Point Extended 3 (74
hex
) – Common service
Service
code
Service available
Service name
Description
Class Instance
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute
10
hex
No
Yes
Set_Attribute_Single Modifies an attribute value
11.2.5.27 Module Configuration (80
hex
)
Instance 0 (Class Attributes)
Table 165: Module Configuration (80
hex
) – Class
Attribute ID Access Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
3
Get
Number of
Instances
UINT
Number of Instances
-