186 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
Instance 1
Table 115: Coupler/Controller configuration (64
hex
) – Instance 1
Attribute ID Acces
s
NV Name
Data type Description
Default
value
5
Get
V
ProcessStat
e
USINT
State of coupler/controller, error
mask:
Bit 0: Local bus error
Bit 3: Module diagnostics (0x08)
Bit 7: Fieldbus error (0x80)
0
6
Get
V
DNS_i_
Trmnldia
UINT
Module diagnostics:
Bit 0..7: Module number
Bit 8..14: Module channel
Bit 15: 0/1 Error, repair/arisen
0
7
Get
V
CnfLen.
AnalogOut
UINT
Number of I/O bits for the analog
output
-
8
Get
V
CnfLen.
AnalogInp
UINT
Number of I/O bits for the analog
input
-
9
Get
V
CnfLen.
DigitalOut
UINT
Number of I/O bits for the digital
output
-
10
Get
V
CnfLen.
DigitalInp
UINT
Number of I/O bits for the digital
input
-
11
Set
NV Bk_Fault_
Reaction
USINT
Fieldbus error reaction
0: stop local I/O cycles
1: set all output to 0
2: no error reaction
3: no error reaction
4: PFC task takes over control of
the outputs (apply to controllers)
1
12..26
Reserved for compatibility to DeviceNet
40..43
Reserved for compatibility to DeviceNet
45
Get
V
Bk_Led_Err
_Code
UINT
I/O LED error code
0
46
Get
V
Bk_Led_Err
_Arg
UINT
I/O LED error argument
0
47
Get
V
Bk_Cfg_Dia
g_
Value
UINT
I/O-Module diagnostics
(Module specific diagnostic
state)
Note:
This attribute has to be
read out before attribute 6
(DNS_i_Trmnldia), because
during the reading of attribute 6
the diagnostic byte contains
the data of the next diagnostic
0