184 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Manual
Version 1.0.0
Instance 3 – Internal Port 3
Table 112: Ethernet link (F6
hex
) – Instance 3
Attribute ID Acces
s
NV
Name
Data type
Description
Default value
1
Get
NV
Interface Speed UDINT
Transfer rate
100
(0x00000064)
2
Get
NV
Interface Flags DWORD
Interface
configuration and
status information
3 (0x03) –
Link active
(Bit 0),
Full duplex
(Bit 1)
3
Get
NV
Physical
Address
ARRAY of 6
UINTs
MAC layer address
MAC ID of the
device
6
Set
NV
Interface
Control
STRUCT of: Configuration of the
physical interface
-
Control Bits
WORD
Interface
configuration bits
3 (0x03) –
Link active
(Bit 0),
Full duplex
(Bit 1)
Forced
Interface Speed
UINT
Baud rate
100 (0x64)
7
Get
NV
Interface Type UINT
Interface type
1 (0x01) –
internal Port
8
Get
NV
Interface State UINT
Interface status
1 (0x01) –
active
9
Get
NV
Admin State
UINT
Admin status
1 (0x01) –
active
10
Get
NV
Interface Label SHORT_
STRING
Name of the interface “Internal Port
3”
11
Get
NV
Interface
Capability
STRUCT of: Properties of the
Ethernet interface
Capability Bits DWORD
Supported
functionsof the
interface
Bit 0: Manual Setting
requires Reset
Bit 1: Auto-Negotiate
Bit 2: Auto-MDIX
Bit 3: Manual
Speed/Duplex
0x00000001
Speed/Duplex
Options
STRUCT of: List of supported
Speed/Duplex
combinations
USINT
Number of the
Speed/Duplex
combinations
1 (0x01)
ARRAY of
STRUCT of:
Supported
Speed/Duplex
combinations
100 Mbit/s FD
(0x64 0x00
0x01)
UINT
Interface Speed
USINT
Interface Duplex
Mode