8.3.4.1 Reasons for Failed IP Address Assignment
•
The PC on whom the BootP server is running is not located in the network
as the fieldbus coupler/controller; i.e., the IP addresses do not match.
Example:
Sub net mask:
255.255.255.0
(default value for a fieldbus
coupler/
controller n)
PC‘s IP:
192.168.
2
.100
fieldbus coupler/controller‘s IP:
192.168.
1
.200
Due to the sub net mask, the first 3 digits of the IP addresses must match.
•
PC and/or head station is/are not linked to the ETHERNET