69
5673 649 - 18
Vitocrossal 300 CU3A 26 to 199 Service
Coding 2
Boiler
Coding in the factory setting
Possible change
06:95
Maximum limit of the boiler
water temperature, specified
in °C by the boiler coding card
06:20
to
06:127
Maximum limit of the boiler water
temperature within the ranges
specified by the boiler.
0D:0
DO NOT ADJUST
--
--
0E:0
DO NOT ADJUST
--
--
13:1
DO NOT ADJUST
--
--
14:1
DO NOT ADJUST
--
--
15:1
DO NOT ADJUST
--
--
21:0
No service interval (hours run)
selected
21:1
to
21:100
Number of hours run before the
burner should be serviced is
adjustable from 100 to 10,000 h
One adjusting step
K
100 h.
23:0
No time interval for burner
service
23:1
to
23:24
Interval adjustable from 1 to 24
months.
24:0
No “Service” display
24:1
“Service” display (the address is
automatically set and must be
manually reset after a service has
been carried out).
2E:0
DO NOT ADJUST
--
--
38:0
Status burner control unit:
Operational (no fault)
38:
≠
0
Status burner control unit: Fault.