Vitocrossal 300 CU3A 26 to 199 Service
5673 649 - 18
60
Coding 1
Heating Circuit 1, 2 and 3
(continued)
Coding in the factory setting
Possible change
Minimum supply temperature heating circuit
C5:20
Electronic minimum supply
temp. limit 68°F (20°C)
C5:1
to
C5:127
Minimum limit adjustable from
34 to 260°F (1 to 127°C)
(limited by boiler-specific
parameters).
Maximum supply temperature heating circuit
C6:74
Electronic maximum supply
temperature limit 165°F
(74°C)
C6:10
to
C6:127
Maximum limit adjustable from
50 to 260°F (10 to 127°C)
(limited by boiler-specific
parameters).
Heating program - changeover
D5:0
The external heating program
changeover changes the
heating program to “Constant
operation with reduced room
temperature” or “Standby
mode”
D5:1
The external heating program
changeover changes to
“Constant operation with
standard room temperature”
(subject to coding address 3A,
3B and 3C).
Ext. heating program changeover to heating circuit
D8:0
No heating program changeover
via extension EA1
D8:1
Heating program changeover
via input DE1 at extension EA1.
D8:2
Heating program changeover
via input DE2 at extension EA1.
D8:3
Heating program changeover
via input DE3 at extension EA1.
Slab curing function (
NOT USED)
F1:0
slab curing function disabled
F1:1
to
F1:6
--
F1:15
--
Party mode time limit
F2:8
Time limit for party mode
or external heating program
changeover via push button:
8 h
*1
F2:0
No time limit for party mode
*1.
F2:1
to
F2:12
Time limit adjustable from 1 to
12 h
*1.
*1
Party mode ends automatically in the “Heating and DHW” program, when the system changes over to
operation with standard room temperature.