Vitocrossal 300 CU3A 26 to 199 Service
5673 649 - 18
56
Coding 1
General
(continued)
Coding in the factory set mode
Possible change
Participant no.
Internal circulation pump function
51:0
System with low loss header:
Internal circulation pump always
starts when there is a heat
demand
51:1
System with low loss header:
When there is a heat demand, the
internal circulation pump is only started
if the burner is operating.
Circulation pump is switched
off after a 60 sec. delay.
51:2
System with heating water
buffer DHW tank:
When there is a heat demand, the
internal circulation pump is only started
if the burner is operating.
Circulation pump is switched
off after a 60 sec. delay.
77:1
LON participant number
77:2
to
77:99
LON participant number,
adjustable from 1 to 99:
1 = Boiler
10 - 98 = Vitotronic 200-H
99= Vitocom
Note:
Allocate each number only once.
Detached house/apartment building
7F:1
Detached house
7F:0
Apartment building
Separate adjustment of holiday program
and time program for DHW heating
possible.
Lock out controls
8F:0
Operation in the standard menu
and extended menu enabled.
Note:
The respective code is only
activated when you exit
the service menu.
8F:1
Operation in standard menu and
extended menu blocked.
Emissions test mode can be enabled.
8F:2
Operation enabled in the standard menu
and blocked in the extended menu.
Emissions test mode can be enabled.
Set supply temperature for external demand
9B:70
Set supply temperature for
external demand 158°F (70°C)
9B:0
to
9B:127
Set supply temperature for external
demand adjustable from 32°F to 260°F
(0°C to 127°C) (limited by boiler-
specific parameters).
Coding in the factory setting
Possible change
Single/multi boiler system
21:0
No service interval (hours run)
selected
21:1
to
21:100
Number of hours run before the burner
should be serviced is adjustable from
100 to 10,000 h
One adjusting step
K
100 h.
Service interval in months
23:0
No time interval for burner
service
23:1
to
23:24
Interval adjustable from 1 to 24 months.
Service status
24:0
No “Service” display
24:1
“Service” display (the address is
automatically set and must be manually
reset after a service has been carried
out).
Boiler