Vitocrossal 300 CU3A 26 to 199 Service
5673 649 - 18
84
Troubleshooting
Checking Outputs (relay tests)
1. Press OK and
simultaneously for approximately
4
sec.
2. “Actuator
test”
The following relay outputs can be controlled subject to system design:
Display
Explanation
Base load
Start
Burner operated at minimum output; heating circuit A1 pump is on.
Full load
Start
Burner operated at maximum output; heating circuit A1 pump is on.
Output, internal
Start
Output
sA
active (DHW Pump) enabled.
Htg circ pump HC2
Start
Heating circuit pump output enabled (extension to heating circuit with mixing
valve)
Mixing valve HC2
Open
“Mixing valve open” output enabled (extension to heating circuit with mixing valve)
Mixing valve HC2
Close
“Mixing valve closed” output enabled (extension to heating circuit with mixing valve)
Htg circ pump HC3
Start
Heating circuit pump output enabled (extension to heating circuit with mixing valve)
Mixing valve HC3
Open
“Mixing valve open” output enabled (extension to heating circuit with mixing valve)
Mixing valve HC3
Close
“Mixing valve closed” output enabled (extension to heating circuit with mixing valve)
Outp. int. exten. H1
Start
Output at internal extension H1 enabled
EA1 output 1
Start
Contact P - S on plug
aBJ
for extension EA1 closed
Solar circuit pump
Start
Solar circuit pump
sF
output at solar control module SM1 enabled
Solar circ pmp min
Start
Solar circuit pump output at solar control module SM1 switched to min. speed
Solar circ pmp max
Start
Solar circuit pump output at solar control module SM1 switched to max. speed
Solar output
sS
Start
Output
sS
at solar control module SM1 enabled
SA 104 output 1
Start
DHW recirculation pump output
sK
SA 104 output 2
Start
Output heating circuit pump A1
sÖ
SA 104 output 3
Start