Vitocrossal 300 CU3A 26 to 199 Service
5673 649 - 18
64
Coding 2
General
(continued)
Coding in the factory setting
Possible change
3A:0
Function input DE1 at extension
EA1: Not assigned
3A:1
Function input DE1: Heating
program - changeover.
3A:2
Function input DE1: External
demand with set supply
temperature. Supply temperature
setting: Coding address 9B.
Internal circulation pump
function: Coding address 3F.
3A:3
Function input DE1: External
blocking. Internal circulation pump
function: Coding address 3E.
3A:4
Function input DE1: External
blocking with fault message input
Internal circulation pump
function: Coding address 3E.
3A:5
Function input DE1: Fault
message input.
3A:6
Function input DE1: Brief
operation, DHW recirculation
pump (push button function
DHW recirculation pump runtime
adjustment: Coding address 3D.
3A:7
Input zone circuit 1, constant
3A:8
Input zone circuit 1, weather
compensated
3B:0
Function input DE2 at extension
EA1: Not assigned
3B:1
Function input DE2: Heating
program - changeover.
3B:2
Function input DE2: External
demand with set supply
temperature. Supply temperature
setting: Coding address 9B.
Internal circulation pump function:
Coding address 3F.
3B:3
Function input DE2: External
blocking. Internal circulation pump
function: Coding address 3E.
3B:4
Function input DE2: External
blocking with fault message input
Internal circulation pump function:
Coding address 3E.
3B:5
Function input DE2: Fault
message input.
3B:6
Function input DE2: Brief
operation, DHW recirculation
pump (push button function).
DHW recirculation pump runtime
adjustment: Coding address 3D.
3A:7
Input zone circuit 1, constant
3A:8
Input zone circuit 1, weather
compensated