Vitocrossal 300 CU3A 26 to 199 Service
Coding 2
General
(continued)
Coding in the factory setting
Possible change
3C:0
Function input DE3 at extension
EA1: Not assigned
3C:1
Function input DE3: Heating
program - changeover.
3C:2
Function input DE3: External
demand with set supply
temperature.
Supply temperature setting:
Coding address 9B.
Internal circulation pump function:
Coding address 3F.
3C:3
Function input DE3: External
blocking.
Internal circulation pump function:
Coding address 3E.
3C:4
Function input DE3: External
blocking with fault message input
Internal circulation pump function:
Coding address 3E.
3C:5
Function input DE3: Fault message
input.
3C:6
Function input DE3: Brief
operation, DHW recirculation
pump (push button function).
DHW recirculation pump runtime
adjustment: Coding address 3D.
3C:7
Input zone circuit 3, constant
3C:8
Input zone circuit 3, weather
compensated
3D:5
DHW recirculation pump
runtime for brief operation: 5
minutes
3D:1
to
3D:60
DHW recirculation pump runtime
adjustable from 1 to 60 minutes.
3E:0
Internal circulation pump
stays in control mode at
signal “External blocking”
3E:1
Internal circulation pump stops
at signal “External blocking”.
3E:2
Internal circulation pump starts
at signal “External blocking”.
3F:0
Internal circulation pump
stays in control mode at
signal “External demand”
3F:1
Internal circulation pump stops
at signal “External demand”.
3F:2
Internal circulation pump starts
at signal “External demand”.
4B:0
Function input
lH
: Room
thermostat (Vitotrol 100) for
constant temperature control
4B:1
External demand.
4B:2
External blocking.
51:0
System with low loss header:
Boiler circuit pump is always
started when there is a heat
demand
51:1
System with low loss header:
When there is heat demand, the
boiler circuit pump will only be
started if the burner is running.
Circulation pump is switched off
when run-on time expires.
51:2
System with heating water buffer
DHW tank:
When there is a heat demand, the
internal circulation pump will only
be started when the burner is
operational.