Vitocrossal 300 CU3A 26 to 199 Service
5673 649 - 18
94
Checking the DHW / low loss header / heating circuit /
room temperature sensor
1. Pull the leads from temperature sensor.
2. Check the sensor resistance and compare it with
the
curve.
3. Replace the sensor in the case of severe deviation.
Temperature sensors
Resistance in k Ohms
Troubleshooting
Corrective Action
(continued)
Temperature sensors
Resistance in k Ohms
Checking the boiler temperature sensor
1. Pull plug
§
and measure the resistance.
2. Check the sensor resistance and compare it with
the
curve.
3. Replace the sensor in the case of severe deviation.
4. Release the strain relief on the sensor well and pull the
sensor out of the well and disconnect plug. Install the
new sensor in reverse order.