Vitocell 100-V, type CVAA, 750 and 950 l capacity
k
b
m
l
BÖ
VA
c
d
e
f
g
h
HR
WW
Z
HV/SPR
KW/E
o
a
b
n
BÖ
Inspection and cleaning aperture
E
Drain
HR
Heating water return
HV
Heating water flow
KW
Cold water
SPR Clamping system for fixing immersion temperature sensors to
the cylinder jacket. Fixing points for 3 immersion temperature
sensors per clamping system
VA
Protective magnesium anode
WW DHW
Z
DHW circulation
Dimensions
Cylinder capacity
l
750
950
Length (
7
)
a
mm
1062
1062
Width
b
mm
1110
1110
Height
c
mm
1897
2197
d
mm
1788
2094
e
mm
1179
1283
f
mm
916
989
g
mm
377
369
h
mm
79
79
k
mm
555
555
l
mm
7
180
7
180
m
mm
513
502
Excl. thermal insulation
n
mm
1005
1005
Excl. thermal insulation
o
mm
7
790
7
790
Performance factor N
L
■ To DIN 4708.
■ Cylinder storage temperature T
cyl
= cold water inlet tempe
50 K
+5 K/-0 K
Cylinder capacity
l
300
500
750
950
Performance factor N
L
at heating water flow temperature
90 °C
9.7
21.0
38.0
44.0
80 °C
9.3
19.0
32.0
42.0
70 °C
8.7
16.5
25.0
39.0
Installation accessories
(cont.)
VITOCAL
VIESMANN
79
5831388
6