Type AWOT-M-E/AWOT-M-E-AC
221.A04
221.A06
221.A08
221.A10
221.A13
221.A16
Secondary circuit connections
(with
connection accessories, female thread)
Heating water flow
G
1¼
1¼
1¼
1¼
1¼
1¼
Heating water return
G
1¼
1¼
1¼
1¼
1¼
1¼
DHW
G
¾
¾
¾
¾
¾
¾
Cold water
G
¾
¾
¾
¾
¾
¾
DHW circulation
G
¾
¾
¾
¾
¾
¾
Outdoor unit flow (heating water outlet)
G
1¼
1¼
1¼
1¼
1¼
1¼
Outdoor unit return (heating water inlet)
G
1¼
1¼
1¼
1¼
1¼
1¼
Length of connection line between in-
door and outdoor units
(Hydraulic con-
nection set)
m
1 to 20
1 to 20
1 to 20
1 to 20
1 to 20
1 to 20
Sound power of outdoor unit
at rated
heating output
(Measurements with reference to
EN 12102/EN ISO 9614-2)
Weighted total sound power level
– At A7
±3 K
/W55
±5 K
(max.)
dB(A)
56
56
58
60
61
61
– At A7
±3 K
/W55
±5 K
in night mode
dB(A)
50
50
50
55
55
55
Energy efficiency class
to EU Regula-
tion no. 813/2013
Heating, average climatic conditions
– Low temperature applications (W35)
A
++
A
++
A
+++
*7
A
+++
*7
A
+++
*7
A
+++
*7
– Medium temperature applications
(W55)
A
+
A
++
A
++
A
++
A
++
A
++
DHW heating, draw-off profile (L)
A
A
A
A
A
A
Performance data
as per EU Regulation
no. 813/2013 (average climatic condi-
tions)
Low temperature applications (W35)
– Energy efficiency η
S
%
173
172
175
176
175
175
– Rated heating output P
rated
kW
5.38
5.59
6.82
9.32
9.99
10.61
– Seasonal coefficient of performance
(SCOP)
4.40
4.38
4.46
4.47
4.46
4.46
Medium temperature applications (W55)
– Energy efficiency η
S
%
124
125
127
129
130
130
– Rated heating output P
rated
kW
5.23
5.59
6.41
9.35
10.07
10.72
– Seasonal coefficient of performance
(SCOP)
3.18
3.21
3.25
3.29
3.32
3.34
– DHW heating energy efficiency η
wh
%
119
119
119
117
117
117
Sound power level to ErP
Sound power level, outdoor unit
dB(A)
53
54
55
56
56
56
Note
Reduced noise night mode can be enabled at the heat pump control
unit at the "Contractor" setting level.
400 V appliances
Type AWOT-E/AWOT-E-AC
221.A10
221.A13
221.A16
Heating performance data
to EN 14511 (A2/W35)
Rated heating output
kW
6.10
6.67
7.02
Fan speed
rpm
600
600
600
Power consumption
kW
1.49
1.64
1.78
Coefficient of performance ε (COP) in heating mode
4.10
4.06
3.94
Output control
kW
4.40 to 10.10
4.80 to 10.60
5.20 to 11.20
Heating performance data
to EN 14511 (A7/W35, 5 K
spread)
Rated heating output
kW
7.58
8.88
10.11
Fan speed
rpm
600
600
600
Air flow rate
m
3
/h
4500
4500
4500
Power consumption
kW
1.51
1.78
2.04
Coefficient of performance ε (COP) in heating mode
5.01
4.99
4.95
Output control
kW
5.45 to 13.60
5.93 to 14.20
6.40 to 14.70
Heating performance data
to EN 14511 (A–7/W35)
Rated heating output
kW
10.09
11.06
11.60
Power consumption
kW
3.17
3.60
3.87
Coefficient of performance ε (COP) in heating mode
3.18
3.07
3.00
*7
The new energy efficiency class A
+++
comes into effect on 26 September 2019.
Vitocal 222-A
(cont.)
20
VIESMANN
VITOCAL
3
5831388