Operating point
W
°C
35
A
°C
–20
–15
–7
2
7
10
20
30
Max. heating output
kW
3.77
4.35
5.70
5.54
6.00
6.86
8.11
9.26
Rated heating output
kW
3.77
4.35
5.70
3.11
4.83
5.00
6.11
7.58
Power consumption
kW
1.89
1.95
1.96
0.82
1.02
1.00
0.98
0.94
Coefficient of performance ε (COP)
1.99
2.23
2.91
3.78
4.72
5.00
6.23
8.10
Min. heating output
kW
1.58
1.79
1.85
2.42
3.01
3.29
4.10
5.15
Operating point
W
°C
45
A
°C
–20
–15
–7
2
7
10
20
30
Max. heating output
kW
3.88
4.38
5.41
5.43
5.06
6.65
7.85
8.93
Rated heating output
kW
3.88
4.38
5.41
3.05
4.49
4.76
5.85
7.27
Power consumption
kW
2.21
2.29
2.40
1.06
1.28
1.26
1.25
1.22
Coefficient of performance ε (COP)
1.75
1.91
2.26
2.87
3.51
3.78
4.67
5.96
Min. heating output
kW
1.64
1.88
2.29
2.28
2.82
3.09
3.90
4.84
Operating point
W
°C
55
A
°C
–20
–15
–7
2
7
10
20
30
Max. heating output
kW
4.47
5.56
5.07
5.79
6.16
7.57
8.58
Rated heating output
kW
4.47
5.56
2.88
4.40
4.53
5.58
6.95
Power consumption
kW
2.67
2.84
1.33
1.51
1.57
1.57
1.55
Coefficient of performance ε (COP)
1.67
1.96
2.17
2.91
2.88
3.54
4.48
Min. heating output
kW
1.83
2.37
2.68
3.14
3.42
4.28
5.30
Operating point
W
°C
60
A
°C
–20
–15
–7
2
7
10
20
30
Max. heating output
kW
5.12
5.15
5.75
6.06
7.41
8.16
Rated heating output
kW
5.12
3.01
4.14
4.44
5.48
6.81
Power consumption
kW
2.89
1.49
1.75
1.76
1.77
1.76
Coefficient of performance ε (COP)
1.77
2.02
2.36
2.52
3.09
3.88
Min. heating output
kW
2.46
3.02
3.38
3.60
4.49
5.32
Cooling
■
Vitocal 200-A
, type AWO-M-E-AC 201.A06
■
Vitocal 222-A
, type AWOT-M-E-AC 221.A06
Cooling capacity at flow temperatures 18 °C, 7 °C
7 °C
18 °C
0
P in kW
20
ϑ in °C
25
30
35
40
45
2
4
6
Power consumption for cooling at flow temperatures 18 °C, 7 °C
2
0
P
el
in kW
ϑ in °C
20
7 °C
18 °C
1
25
30
35
40
45
Performance factor EER at flow temperatures of 18 °C, 7 °C
EER
ϑ in °C
20
0
8
7 °C
18 °C
2
4
6
25
30
35
40
45
ϑ
Air intake temperature
P
Cooling capacity
P
el
Power consumption
EER Coefficient of performance
Note
■ The EER data in the tables and diagrams was calculated with ref-
erence to EN 14511.
■ Performance characteristics apply to new appliances with clean
plate heat exchangers.
Curves
(cont.)
32
VIESMANN
VITOCAL
5
5831388