Type AWO/AWO-E/AWO-E-AC
201.A10
201.A13
201.A16
Heating water
(secondary circuit)
Minimum flow rate
l/h
1400
1400
1400
Minimum volume in the heating system, cannot be fitted
with shut-off devices
l
50
50
50
Max. external pressure drop (RFH) at minimum flow rate
mbar
500
500
500
kPa
50
50
50
Max. flow temperature
°C
60
60
60
Outdoor unit electrical values
Rated voltage, compressor
3/N/PE 400 V/50 Hz
Max. operating current, compressor
A
8.7
8.7
8.7
Cos φ
0.96
0.96
0.96
Starting current, compressor
A
15
15
15
Fuse rating
B16 A
B16 A
B16 A
IP rating
IP X4
IP X4
IP X4
Indoor unit electrical values
Heat pump control unit/PCB
– Rated voltage, control unit/PCB
1/N/PE 230 V/50 Hz
– Power supply fuse rating
1 x B16A
1 x B16 A
1 x B16 A
– Internal fuse
6.3 A (slow)/250 V
Instantaneous heating water heater
– Type AWO-E/AWO-E-AC:
Factory-fitted
– Type AWO:
Accessories
– Rated voltage
1/N/PE 230 V/50 Hz
or
3/N/PE 400 V/50 Hz
– Heating output
kW
9
9
9
– Power supply fuse rating
3 x B16A
3 x B16 A
3 x B16 A
Max. power consumption
Fan
W
2 x 45
2 x 45
2 x 45
Outdoor unit
kW
5.13
5.13
5.15
Secondary pump (PWM)
W
60
60
60
– Energy efficiency index EEI
≤ 0.2
≤ 0.2
≤ 0.2
Control unit/PCB, outdoor unit
W
15
15
15
Control unit/PCB, indoor unit
W
10
10
10
Control unit/PCB power, indoor unit
W
1000
1000
1000
Refrigerant circuit
Refrigerant
R410A
R410A
R410A
– Refrigerant charge
kg
2.40
2.40
2.40
– Global warming potential (GWP)
*3
1924
1924
1924
– CO
2
equivalent
t
4.6
4.6
4.6
Compressor (hermetically sealed)
Type
Scroll
Scroll
Scroll
– Oil in compressor
Type
3 MAF POE
3 MAF POE
3 MAF POE
– Quantity of oil in compressor
l
1.17
1.17
1.17
Permissible operating pressure
– High pressure side
bar
43
43
43
MPa
4.3
4.3
4.3
– Low pressure side
bar
28
28
28
MPa
2.8
2.8
2.8
Outdoor unit dimensions
Total length
mm
546
546
546
Total width
mm
1109
1109
1109
Total height
mm
1377
1377
1377
Indoor unit dimensions
Total length
mm
370
370
370
Total width
mm
450
450
450
Total height
mm
880
880
880
Total weight
Outdoor unit
kg
153
153
153
Indoor unit
– Type AWO
kg
40
40
40
– Type AWO-E/AWO-E-AC
kg
41
41
41
Permissible operating pressure
, secondary side
bar
3
3
3
MPa
0.3
0.3
0.3
*3
Based on the Fifth Assessment Report of the Intergovernmental Panel on Climate Change (IPCC)
Vitocal 200-A
(cont.)
12
VIESMANN
VITOCAL
2
5831388