65
Coding in the delivered condition
Possible change
Screed function
F1:0
Screed function disabled F1:1
to
F1:6
Screed function adjustable
in accordance with 6
optional temperature/time
profiles (see page 120)
F1:15
Constant flow temperature
20 °C
Party mode time limit
F2:8
Time limit for party mode
or external heating pro-
gram changeover via key:
8 h
*1
F2:0
No time limit for party
mode
*1
F2:1
to
F2:12
Time limit adjustable from 1
to 12 h
*1
Start temperature raising
F8:-5
Temperature limit for ter-
minating reduced mode
-5 ºC, see example on
page 122.
Observe the setting of
coding address "A3".
F8:+10
to
F8:-60
Temperature limit adjusta-
ble from
+10 to -60 °C
F8:-61
Function disabled
End temperature raising
F9:-14
Temperature limit for rais-
ing the reduced set room
temperature -14 ºC, see
example on page 122.
F9:+10
to
F9:-60
Temperature limit for rais-
ing the set room tempera-
ture to the value selected
for standard mode adjusta-
ble from
+10 to -60 °C
Increase set flow temperature
FA:20
Raising the set boiler
water temperature or the
set flow temperature
when changing from
operation with reduced
room temperature to
operation with standard
room temperature, by
20 %. See example on
page 123.
FA:0
to
FA:50
Temperature rise adjusta-
ble from 0 to 50 %
*1
Party mode ends automatically in the "Heating and DHW" program, when the
system changes over to operation with standard room temperature.
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5692 860 GB