108
10
1
10 30 50 70 90 110
Temperature in °C
0.4
0.6
0.8
2
4
6
8
20
Resistance in kΩ
3.
Replace the sensor in the case of
severe deviation.
Checking the flue gas temperature sensor
The flue gas temperature sensor locks out the boiler when the permissible flue gas
temperature is exceeded. Reset the interlock after the flue system has cooled down
by pressing reset button
R
.
1.
Pull the leads from flue gas tempera-
ture sensor
A
.
Troubleshooting
Repairs
(cont.)
5692 860 GB