68
Value
address
00: ...
System
version
Description
1
1
One heating circuit without mixer (heating circuit 1), without
DHW heating
2
1
One heating circuit without mixer (heating circuit 1), with DHW
heating (code is adjusted automatically)
3
2
One heating circuit with mixer (heating circuit 2), without DHW
heating
4
2
One heating circuit with mixer (heating circuit 2), with DHW
heating
5
2
One heating circuit without mixer (heating circuit 1) and one
heating circuit with mixer (heating circuit 2), without DHW
heating (code is adjusted automatically)
6
2
One heating circuit without mixer (heating circuit 1) and one
heating circuit with mixer (heating circuit 2), with DHW heating
(code is adjusted automatically)
7
3
One heating circuit with mixer (heating circuit 2) and one heat-
ing circuit with mixer (heating circuit 3), without DHW heat-
ing
8
3
One heating circuit with mixer (heating circuit 2) and one heat-
ing circuit with mixer (heating circuit 3), with DHW heating
9
3
One heating circuit without mixer (heating circuit 1), one heat-
ing circuit with mixer (heating circuit 2) and one heating circuit
with mixer (heating circuit 3), without DHW heating (code is
adjusted automatically)
10
3
One heating circuit without mixer (heating circuit 1), one heat-
ing circuit with mixer (heating circuit 2) and one heating circuit
with mixer (heating circuit 3), with DHW heating (code is
adjusted automatically)
Coding in the delivered condition
Possible change
11:
≠
9
No access to the coding
addresses for the com-
bustion controller param-
eters
11:9
Access open to the coding
addresses for the combus-
tion controller parameters
32:0
Never adjust
35:0
Without extension EA1
35:1
With extension EA1 (auto-
matic recognition)
36:0
Function output
aBJ
at
extension EA1: Fault
message
36:1
Function output
aBJ
: Feed
pump
Code 2
General
(cont.)
5692 860 GB