97
Displayed
fault code
System characteris-
tics
Cause
Measures
92
No solar DHW heat-
ing
Short circuit, col-
lector temperature
sensor
Check temperature sen-
sor
&
on solar control
module or Vitosolic sen-
sor
93
Control mode
Short circuit, cylin-
der temperature
sensor
Check temperature sen-
sor at connection S3 to
Vitosolic 100
94
No solar DHW heat-
ing
Short circuit, cylin-
der temperature
sensor
Check temperature sen-
sor
%
on solar control
module or Vitosolic sen-
sor
98
Control mode
Lead break, tem-
perature sensor
/
Check sensor
/
on solar
control module
99
Control mode
Lead break, tem-
perature sensor
aÖ
Check sensor
aÖ
on solar
control module
9A
No solar DHW heat-
ing
Lead break, collec-
tor temperature
sensor
Check temperature sen-
sor
&
on solar control
module or Vitosolic sen-
sor
9b
Control mode
Lead break, cylin-
der temperature
sensor
Check temperature sen-
sor at connection S3 to
Vitosolic 100
9C
No solar DHW heat-
ing
Lead break, cylin-
der temperature
sensor
Check temperature sen-
sor
%
on solar control
module or Vitosolic sen-
sor
9E
Control mode
No flow rate in col-
lector circuit or flow
rate too low, or
temperature limiter
has responded
Check solar circuit pump
and solar circuit. Acknowl-
edge fault message.
9F
Control mode
Solar control mod-
ule or Vitosolic
faulty
Replace solar control
module or Vitosolic
A7
Control mode as per
delivered condition
Programming unit
faulty
Replace programming
unit
b0
Burner blocked
Short circuit, flue
gas temperature
sensor
Check flue gas tempera-
ture sensor
Troubleshooting
Fault codes
(cont.)
5692 860 GB