119
Heating program - changeover
Code
No heating program changeover
F2:0
Duration of the heating program changeover 1 to 12 hours
F2:1 to
F2:12
The heating program changeover stays
enabled for as long as the contact
remains closed, but at least as long as
the duration selected in coding address
"F2".
External blocking
The "External blocking" and "External
blocking and fault message input" func-
tions are connected via extension EA1.
There are 3 inputs available at extension
EA1 (DE1 to DE3).
The function is selected via the following
codes:
External blocking
Code
Input DE1
3A:3
Input DE2
3b:3
Input DE3
3C:3
External blocking and fault message input
Code
Input DE1
3A:4
Input DE2
3b:4
Input DE3
3C:4
The effect on a circulation pump for cyl-
inder heating is selected with code 5E.
The effect on the relevant heating circuit
pump is selected with code d6.
External demand
The "External demand" function is con-
nected via extension EA1. There are 3
inputs available at extension EA1 (DE1
to DE3).
The function is selected via the following
codes:
Function description
Control functions
(cont.)
5692 860 GB
Summary of Contents for CU3A
Page 147: ...147 5692 860 GB ...