![Viessmann CU3A Service Instructions For Contractors Download Page 138](http://html.mh-extra.com/html/viessmann/cu3a/cu3a_service-instructions-for-contractors_1016864138.webp)
138
Setting and test val-
ues
Set value
Commis-
sioning
Mainte-
nance/serv-
ice
Date:
By
Static pressure
mbar
max. 57.5
Supply pressure (flow
pressure)
=
for natural gas E
mbar
17.4-25
=
for natural gas LL
mbar
17.4-25
=
for LPG
mbar
42.5-57.5
Tick gas type
Carbon dioxide con-
tent CO
2
For natural gas E and
LL
■ at lower output
% by
vol.
7.7-9.2
■ at upper output
% by
vol.
7.7-9.2
For LPG
■ at lower output
% by
vol.
9.3-10.9
■ at upper output
% by
vol.
9.3-10.9
Oxygen content O
2
■ at lower output
% by
vol.
4.4-6.9
■ at upper output
% by
vol.
4.4-6.9
Carbon monoxide
content CO
■ at lower output
ppm
< 60
■ at upper output
ppm
< 60