Coding in the delivered condition
Possible change
0d:1
Night circulation monitor-
ing switched on.
Unintentional flow rate is
captured in the collector
circuit (e.g. at night).
0d:0
Night circulation monitor-
ing switched off.
0E:1
Calculation of solar yield
with Viessmann heat
transfer medium
0E:2
Calculation of solar yield
with water as heat transfer
medium (do not select as
operation is only possible
with Viessmann heat trans-
fer medium)
0E:0
Calculation of solar yield
switched off
0F:70
The flow rate in the col-
lector circuit at the maxi-
mum pump speed is set
to 7 l/min.
0F:1
to
0F:255
Flow rate in the collector
circuit adjustable from 0.1
to 25.5 l/min
10:0
Target temperature con-
trol switched off (see cod-
ing address 11)
10:1
Target temperature control
switched on
11:50
Set cylinder temperature
for solar 50 °C.
■ Target temperature
control switched on
(code 10:1):
Temperature at which
the solar heated water
in the DHW cylinder is
to be stratified.
■ Extended control func-
tions set to heat two
DHW cylinders (code
20:8):
If the actual tempera-
ture of a DHW cylinder
reaches the selected
set cylinder tempera-
ture, heating is trans-
ferred to the second
DHW cylinder.
11:10
to
11:90
The set cylinder tempera-
ture for solar can be adjus-
ted from 10 to 90 °C
Code 2
Solar
(cont.)
5692 860 GB