Parameters for circulation pumps and other components
Heating circuit pump
Parameter
Setting
"System definition"
Ó
"System scheme 7000"
■
With heating circuit HC1 without mix-
er
or
■
With heating circuit HC2 with mixer
or
■
With heating circuit HC3 with mixer
DHW circulation pump
Parameter
Setting
Extended menu
Ó
"Time program DHW circulation"
Set a time program.
Installation kit with mixer for heating circuit M2/HC2
Parameter
Setting
"System definition"
Ó
"Type of assembly kit 7044"
"1"
"Internal hydraulics"
Ó
"Rated output heating circuit pump HC2 734A"
Set the required rated output in %.
Mixer extension kit for heating circuit M3/HC3
Parameter
Setting
"System definition"
Ó
"System scheme 7000"
With heating circuit HC3
Note
Set rotary switch S1 in the extension
kit to "2": See "Mixer extension kit" in-
stallation instructions.
Remote control for heating/cooling circuit or Vitocomfort 200
Parameter
Setting
"Heating circuit 1"
/
"Heating circuit 2"
/
"Heating circuit 3"
Ó
"Remote control 2003"
or
"Remote control 3003"
or
"Remote control 4003"
"1"
Note
To assign a heating circuit, set the
code at the remote control:
See "Vitotrol" installation instructions.
Room temperature sensor for separate cooling circuit
Parameter
Setting
"Cooling"
Ó
"Ranking room temp sensor separate cooling circuit 7106"
"0"
Connection F16
"1"
Heating circuit HC1
"2"
Heating circuit HC2
"3"
Heating circuit HC3
"4"
Do not adjust.
Commissioning, inspection, maintenance
Commissioning the system
(cont.)