139
Heating circuit 3
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
Standard room temperature
4000
200 (
≙
20 °C)
Reduced room temperature
4001
200 (
≙
20 °C)
Remote control
4003
0
Room temperature control
4005
0 Without remote
control
2 With remote con-
trol
Heating curve level
4006
0 (
≙
0 K)
Heating curve slope
4007
6 (
≙
0.6)
Influence room temperature hook-up
400A
10
Room temperature hook-up
400B
0
Max. flow temperature heating circuit
400E
550 (
≙
55 °C)
Runtime mixer heating circ
4015
Do not adjust.
Room temperature in party mode
4022
160 (
≙
16 °C)
Cooling
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
"Cooling function"
7100
0
"Cooling circuit"
7101
1
"Set room temperature separate cooling
circuit"
7102
200 (
≙
20 °C)
"Min. flow temperature cooling"
7103
200 (
≙
20 °C)
"Influence room temperature hook-up
cooling circuit"
7104
0
"Room temperature control cooling cir-
cuit"
7105
1
"Ranking room temp sensor separate
cooling circuit"
7106
0
"Hysteresis room temp cooling circuit"
7107
10 (
≙
1 K)
"Enable flow temperature sensor cooling
circuit"
7109
1
"Cooling curve level"
7110
0 (
≙
0 K)
"Cooling curve slope"
7111
12 (
≙
1.2)
"Remote control cooling circ"
7116
Never adjust
"Enable active cooling"
71FE
0
Ventilation: Vitovent 200-C and Vitovent 300-F
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
Vitovent enable
7D00
0
Enable preheater bank electric
7D01
0
Enable reheater bank hydraulic
7D02
0
Enable target temperature control
7D04
0
Enable humidity sensor
7D05
0
Enable CO2 sensor
7D06
0
Set room temperature
7D08
200 (
≙
20 °C)
Commissioning/service reports
Control parameter report
(cont.)
51
17 700 GB
Appendix