136
DHW
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
"Set DHW temperature"
6000
500 (
≙
50 °C)
"Min. DHW temperature"
6005
100 (
≙
10 °C)
"Max. DHW temperature"
6006
600 (
≙
60 °C)
"Hysteresis DHW temperature heat
pump"
6007
50 (
≙
5 K)
"Hysteresis DHW temperature booster
heater"
6008
100 (
≙
10 K)
"Start optimisation for DHW heating"
6009
0
"Stop optimisation for DHW heating"
600A
0
"Set DHW temperature 2"
600C
600 (
≙
60 °C)
"Temperature rise per hour for DHW
heating"
600D
30 K/h
"Temperature sensor at bottom of DHW
cylinder"
600E
0
"Max. runtime DHW heating in heating
mode"
6011
240 (
≙
24 min)
"Max. interruption of DHW heating for
central heating"
6012
90 (
≙
9 min)
"Enable booster heaters for DHW heat-
ing"
6014
0
"Enable electric heaters for DHW heat-
ing"
6015
0
"Priority DHW heating with combi cylin-
der"
6016
0
"Start attempts for DHW after high pres-
sure shutdown"
6017
0
"Shutdown hysteresis inst. heating water
heater"
601E
10 (
≙
1 K)
"Enable elec. heating/ext. HS for reheat-
ing only"
6040
0
Electric booster heater
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
"Enable instantaneous heating water
heater"
7900
1
"Enable electric heaters for DHW heat-
ing"
7901
0
"Enable instant. heating water heater for
central heating"
7902
0
"Start delay instantaneous heating water
heater"
7905
30 min
"Max. output instantaneous heating wa-
ter heater"
7907
3
"Output for instant. heating water heater
at power-OFF"
790A
0
"Dual mode temp. instant. heating water
heater"
790B
500 (
≙
50 °C)
Commissioning/service reports
Control parameter report
(cont.)
51
17 700 GB
Appendix