141
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
Background ventilation
C109
■
Vitovent 200-W:
15 %
■
Vitovent 300-C:
30 m
3
/h
■
Vitovent 300-W:
50 m
3
/h
Reduced ventilation
C10A
■
Vitovent 200-W:
25 %
■
Vitovent 300-C:
75 m
3
/h
■
Vitovent 300-W:
100 m
3
/h
Standard ventilation
C10B
■
Vitovent 200-W:
50 %
■
Vitovent 300-C:
100 m
3
/h
■
Vitovent 300-W:
150 m
3
/h
Intensive ventilation
C10C
■
Vitovent 200-W:
75 %
■
Vitovent 300-C:
125 m
3
/h
■
Vitovent 300-W:
225 m
3
/h
Background ventilation, second fan duct
C189
15 %
Reduced ventilation, second fan duct
C18A
25 %
Standard ventilation, second fan duct
C18B
50 %
Intensive ventilation, second fan duct
C18C
75 %
Bypass mode
C1A0
0
Central heating and heat recovery
C1A1
0
Imbalance permitted
C1A2
1
Specified imbalance
C1A3
0
Set reheater coil temperature
C1A4
210 (
≙
21 °C)
Humidity sensor sensitivity
C1A6
0
Min. temperature, geothermal heat ex-
changer
C1AA
50 (
≙
5 °C)
Max. temperature, geothermal heat ex-
changer
C1AB
250 (
≙
25 °C)
Function, input 1
C1B0
0
Min. voltage, input 1
C1B1
0 (10
≙
1 V)
Min. voltage, input 2
C1C1
0 (10
≙
1 V)
Flow rate correction
C1C7
100
Commissioning/service reports
Control parameter report
(cont.)
51
17 700 GB
Appendix