137
Internal hydraulics
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
Heat pump for drying a building
7300
0
Time program for screed drying
7303
0
Set flow temperature external demand, cool-
ing
730A
Do not adjust.
Set flow temperature external demand
730C
500 (
≙
50 °C)
Start threshold
730E
300 (
≙
30 K x min)
Compressor performance at min. outside
temperature
730F
50 %
Compressor performance at max. outside
temperature
7310
20 %
Cycle rate heating circuit pumps
7319
0
Rated output heating circuit pump HC2
734A
60 %
Starting time high efficiency circulation
pump
7365
Do not adjust.
Screed program start day
7378
1
Screed program end day
7379
31
Primary source
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
"Primary source ctrl strategy"
7401
Never adjust
Heating water buffer cylinder
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
"Enable buffer cylinder/low loss header"
7200
0
"Temp in operating status fixed value for
buffer cyl"
7202
500 (
≙
50 °C)
"Hysteresis temperature heating buffer
cylinder"
7203
50 (
≙
5 K)
"Max. temperature buffer cylinder"
7204
600 (
≙
60 °C)
"Stop optimisation heating buffer cylin-
der"
7205
0
"Temp. limit op. status fixed value for
buffer cylinder"
7208
500 (
≙
50 °C)
"Stop hysteresis, heating water buffer
cylinder"
7209
0 (
≙
0 K)
"Operating mode, fixed value only for
heat demand"
720A
0
Commissioning/service reports
Control parameter report
(cont.)
51
17 700 GB
Appendix