External hook-up for heating/cooling circuits
Parameter
Setting
"Heating circuit 1"
/
"Heating circuit 2"
/
"Heating circuit 3"
Ó
"Remote control 2003"
or
"Remote control 3003"
or
"Remote control 4003"
"2"
Type AWBT(-M)-E-AC: Cooling function parameters
Parameter
Setting
"Cooling"
Ó
"Cooling function 7100"
"3"
"Cooling circuit 7101"
"1"
Heating circuit HC1
"2"
Heating circuit HC2
"3"
Heating circuit HC3
"4"
Separate cooling circuit SKK
Parameters for instantaneous heating water heater
Parameter
Setting
"Electr booster heater"
Ó
"Enable instantaneous heating water heater 7900"
"1"
"Output for instant. heating water heater at power-OFF 790A" "1"
3 kW
"2"
6 kW
"3"
9 kW
Enable instantaneous heating water heater for DHW heating
Parameter
Setting
"DHW"
Ó
"Enable electric heaters for DHW heating 6015"
"1"
Parameters for swimming pool water heating
Parameter
Setting
"System definition"
Ó
"External extension 7010"
"1"
or
"3"
"Swimming pool 7008"
"1"
Parameters for ventilation with Vitovent 200-C
Parameter
Setting
"Ventilation"
Ó
"Vitovent enable 7D00"
"2"
Vitovent 200-C
Commissioning, inspection, maintenance
Commissioning the system
(cont.)