151
Type AWBT/AWBT-E/AWBT-E-AC
221.C10
221.C13
221.C16
Refrigerant line connections
Liquid line
■
Pipe
7
mm
10 x 1
10 x 1
10 x 1
■
Indoor unit
UNF
⅝
⅝
⅝
■
Outdoor unit
UNF
⅝
⅝
⅝
Hot gas line
■
Pipe
7
mm
16 x 1
16 x 1
16 x 1
■
Indoor unit
UNF
⅞
⅞
⅞
■
Outdoor unit
UNF
⅞
⅞
⅞
Length of liquid line and hot gas line
■
Heating mode
m
3 to 30
3 to 30
3 to 30
■
Cooling mode
m
3 to 30
3 to 30
3 to 30
Sound power of outdoor unit
at rated heating output
(Measurements with reference to EN 12102/
EN ISO 9614-2)
Weighted total sound power level
■
At A7
±
3 K
/W55
±
5 K
(max.)
dB(A)
61
61
61
■
At A7
±
3 K
/W55
±
5 K
in night mode
dB(A)
55
55
55
Energy efficiency class
to EU Regulation no.
811/2013
Heating, average climatic conditions
■
Low temperature applications (W35)
A
++
A
++
A
++
■
Medium temperature applications (W55)
A
++
A
++
A
++
DHW heating, draw-off profile (L)
A
A
A
Performance data
as per EU Regulation
no. 811/2013 (average climatic conditions)
Low temperature applications (W35)
■
Energy efficiency
η
S
%
180
183
182
■
Rated heating output P
rated
kW
9.75
11.17
Medium temperature applications (W55)
■
Energy efficiency
η
S
%
132
131
134
■
Rated heating output P
rated
kW
9.67
10.83
11.98
Sound power level to ErP
Sound power level, outdoor unit
dB(A)
56
56
56
Specification
Specification
(cont.)
51
17 700 GB
Appendix