148
400 V appliances
Type AWBT/AWBT-E/AWBT-E-AC
221.C10
221.C13
221.C16
Heating performance data
to EN 14511
(A2/W35)
Rated heating output
kW
5.90
6.31
7.02
Fan speed
rpm
600
600
600
Power consumption
kW
1.44
1.59
1.78
Coefficient of performance
ε
(COP) in heating
mode
4.10
3.98
3.94
Output control
kW
3.50 to 10.50
4.00 to 11.40
4.50 to 12.00
Heating performance data
to EN 14511
(A7/W35, 5 K spread)
Rated heating output
kW
7.58
8.61
10.11
Fan speed
rpm
600
600
600
Air flow rate
m
3
/h
4500
4500
4500
Power consumption
kW
1.51
1.77
2.04
Coefficient of performance
ε
(COP) in heating
mode
5.01
4.87
4.95
Output control
kW
4.70 to 13.60
5.20 to 14.20
5.70 to 14.70
Heating performance data
to EN 14511
(A
–
7/W35)
Rated heating output
kW
10.09
10.74
11.60
Power consumption
kW
3.17
3.58
3.87
Coefficient of performance
ε
(COP) in heating
mode
3.18
3.00
3.00
Cooling performance data
to EN 14511
(A35/W7)
Rated cooling capacity
kW
4.92
6.11
7.02
Fan speed
rpm
600
600
600
Power consumption
kW
1.82
2.20
2.53
Energy efficiency ratio EER in cooling mode
2.70
2.78
2.77
Output control
kW
Up to 6.0
Up to 6.5
Up to 7.1
Cooling performance data
to EN 14511
(A35/W18)
Rated cooling capacity
kW
6.20
7.55
10.00
Fan speed
rpm
600
600
600
Power consumption
kW
1.77
2.29
3.57
Energy efficiency ratio EER in cooling mode
3.50
3.30
2.80
Output control
kW
Up to 8.0
Up to 9.5
Up to 10.5
Air intake temperature
Cooling mode (type AWBT-E-AC only)
■
Min.
°C
15
15
15
■
Max.
°C
43
43
43
Heating mode
■
Min.
°C
–
20
–
20
–
20
■
Max.
°C
35
35
35
Specification
Specification
(cont.)
51
17 700 GB
Appendix