Information for the user – Troubleshooting
Error
Cause of Error
Troubleshooting
In cloudy conditions, shade
moves into its upper end position
too early
Threshold for retract sun
function is set too low
Response time setting is too
short
Raise threshold for retract
sun function (see p. 47)
Increase sun function response
time (see p. 47)
Sunshade does not automatically
move into its upper position in the
evening
Retract threshold setting is
too low
Lux sensor is affected by
strong light source
Sunshade has been lowered
manually
Raise threshold for retract
sun function (see p. 47)
Check the lux sensors’
readings (see p. 47)
Retract the sunshade manually
Check automatic lock
(see p. 62)
Skylight opens too late
Temperature threshold setting
for ‘open skylight’ is too high
Decrease threshold for
temperature function
(see p. 52)
Skylight only partially opens
Temperature threshold 2 for
skylight has been exceeded
Decrease temperature
threshold 1 for skylight function
(see p. 52)
Increase motor runtime for
skylight function (see p. 53)
No automatic retraction of
sunshade during rain when in
manual mode
Rain/frost alarm not active
in manual mode
Change rain/frost alarm setting
for manual mode (see. p. 49)
Connected sunshades extend
for only 3 seconds in response
to sun / temperature
MC DZ M/J function is active
Runtime is set to 3 seconds
Deactivate MC DZ M/J
function (see p. 58)
Adjust sunshade runtime
(see pp. 48, 53 and 54)