Information for the user – Troubleshooting
Error
Cause of Error
Troubleshooting
Control system does not function
Power failure
Fault in the connection area of
the control system
Wait until power supply is
restored
Check 160 mA T fine-wire fuse
(F1) and replace if necessary
Check connection according
to wiring diagram (see p. 10)
Connected motors do not move
in or out,
skylights do not open or close
Fine-wire fuse in the motor box
is faulty
No wire bridge between
Common and L1 (only in the
case of direct motor connection!)
Check 6.3 A T fine-wire fuse
(F2) and replace if necessary
Check wire bridge between
Common and L1 (see p. 13)
No display box display
Fault in the connection of
the 4-wire interface
Check connection according
to wiring diagram (see p. 10)
See p. 26
Display turns off after short
period
Standby time set to 1 minute
Adjust standby time to required
level (see p. 40)
No or insufficient radio-controlled
clock reception
Signal strength is too low
Check connection according
to wiring diagram (see p. 22)
Change the mounting position
of the DCF 77 radio-controlled
clock receiver (see p. 22)
48 h wind sensor alarm display
Wind sensor blocked
No wind over the last 48 hours
Check the affected wind sensor
(see p. 66)
Wind sensor cable rupture
display
Wind sensor’s connecting
cable damaged
Fault in connection area
Check connection according
to wiring diagram (see p. 10)
Check connecting cable for
damage (see p. 66)
Lux sensor cable rupture display
Lux sensor’s connecting
cable damaged
Fault in connection area
Check connection according
to wiring diagram (see p. 10)
Check connecting cable for
damage (see p. 66)
Wind speed display too low
Wind sensor is not positioned
fully in the area of wind flow
Incorrect wind sensor type
is set
Check the wind sensor position
and change if necessary
(see p. 15)
Check the smooth running
of the wind wheel (see p. 66)
Check settings in the wizard
(see p. 32)
Lux sensor displays readings
that are too low
Lux sensor is in the shade
Lux sensor is soiled or covered
Check the lux sensor position
and change if necessary
(see p. 17)
Remove any soiling (see p. 17)