9
Turn on the devices in the proper sequence as described in this section.
See
“Turning on the hardware and verifying operation”
on page 77.
10
Add the new disk space with the instructions in one of these sections.
See
“Adding the disk space of an Expansion Storage Shelf from the NetBackup
on page 115.
See
“Adding the disk space of an Expansion Storage Shelf from the NetBackup
on page 117.
Connecting one Expansion Shelf to a system that
has two existing Expansion Shelves
Expansion Shelves connect to the Primary Shelf and to other Expansion Shelves
but they do not connect directly to the compute node.
To connect a new Expansion Shelf to a Primary Shelf and to two existing
Expansion Shelves
1
Verify that all compute nodes and the Primary Shelf are off and that the power
cords are unplugged. Do not remove the cables between the compute nodes
and the Primary Shelf.
Do not remove the cables between the compute nodes and the Primary Shelf.
2
Obtain the two SAS-3 cables that ship with each Expansion Shelf.
3
Identify the single SAS-3 port on the left side of each controller module in the
Primary Shelf.
4
Identify ports A and C in each I/O module in the Expansion Shelf. Port B is not
available for use.
111
Adding Expansion Storage Shelves to an operating appliance that has at least one operating Expansion shelf
Connecting one Expansion Shelf to a system that has two existing Expansion Shelves