IMPORTANT: Note the correct orientation of the blue tab on the ends of the
SAS-3 cables. The blue tab must face down in the ports on all shelves.
6
Connect the cables as follows:
■
Connect one cable to each of the SAS-3 ports on the left of each controller
module on the Primary Shelf.
■
Connect the left cable to port A in the left I/O module on the closest
Expansion Shelf.
■
Connect the right cable from the Primary Shelf to port A in the right I/O
module in the farthest Expansion Shelf.
■
Connect one end of a new cable to port C in the left module of the first
Expansion Shelf.
■
Connect one end of another cable to port A on the right I/O module of the
first Expansion Shelf.
■
Connect the other end of that cable to port C in the right I/O module of the
second Expansion Shelf.
■
Connect one end of another cable to port C on the left I/O module of the
second Expansion Shelf.
■
Connect the other end of that cable to port A in the left I/O module of the
third Expansion Shelf.
■
Connect one end of another cable to port A on the right I/O module of the
second Expansion Shelf.
■
Connect the other end of that cable to port C in the right I/O module of the
third Expansion Shelf.
99
Adding Expansion Storage Shelves to an operating appliance that does not have any Expansion shelves
Connecting three Expansion Shelves to the Primary Shelf