Tips: in the process of frequency inverter start and speed up, when the given
frequency is lower than start-up frequency, frequency inverter output is
zero.
E-30
Start-up selection
Range :0~2
Factory
setting:0
0: Start by the start-up frequency [E-28] the start-up frequency setting
and [E-29] start-up frequency duration setting control frequency inverter
start; It is suitable for the situation with big static friction torque
and small load inertia, or the situation where it need to coordinate with
exterior machinery braking devices. That is occasion where the motor shaft
can maintain static before the motor restart after close down.
1: DC braking first, then start-up frequency Firstly, DC braking voltage
[E-35] and DC braking time [E-38] give the motor with load a certain DC
braking energy (namely electromagnetic brake), then start by start-up
frequency; It is suitable for the small inertial load occasion with forward
rotating or reversing phenomenon in the stop state.