156
[ H-28 ] setting
value, alarm
Err1
Open-phas
e at input
side
Open-phase
in
frequency
inverter
three phase input
power Phase.
Check three phase input power and
three phase input power wiring
Err2
Output
grounding
Frequency
inverter
has device grounding
short circuit at the
output side;
Check peripheral device
、 grounding line 、 machine
insulation;
Err3
Current
detecting
fault
1.Detecting circuit
fault;
2.Damaged
HALL
component;
1. Ask for technical support;
2. Ask for technical support;
Err4
Frequency
inverter
exterior
fault
Exterior exterminal
action;
Check exterior device;
Err5
Swing
frequency
running
parameter
s setting
error
User set the swing
running parameter
not correctly;
Reset the swing frequency
running parameters;
Err6
Keyboard
communica
tion
fault
1.Keyboard
wiring
fault;
2.Keyboar
communication
component damaged;
1.Check the keyboard wiring;
2.Ask for technical support;
93SE
Memorizer
fault
1. Read/write error
of keyboard control
parameters;
1.Frequency
inverter
re-electrify;
2.Ask for technical support;
Summary of Contents for AC60 series
Page 1: ...Manual AC60 series frequency inverter Version V2 0...
Page 30: ...26...
Page 44: ...40 2 Double display keyboard cycle switch the display of monitoring parameter mode...
Page 46: ...42 2 Double display keyboard parameter setting mode...
Page 162: ...158 8 2 2 Over current...
Page 163: ...159 8 2 3 Over voltage...
Page 164: ...160 8 2 4 Supply voltage is too low...
Page 165: ...161 8 2 5 Inner inverter over heat...
Page 166: ...162 8 2 6 Over load...
Page 167: ...163 8 2 7 No display 8 2 8 Motor heat...
Page 168: ...164 8 2 9 Motor does not rotate...