153
inertia is too big;
3. Frequency inverter
capacity is too low;
;
3.Select frequency inverter with
proper capacity;
o.C.3
Over
current
at
constant
speed
1.Load
change
suddenly;
2.Network voltage is
relatively low.
1. Check the load change
condition and eliminate it;
2.Check the input power;
o.U.1
Acc over
voltage
1.Supply
voltage
overrun;
2.
Restart
the
machine in running
(
no
tracking
start)
;
1.Check the network voltage ,
troubleshooting;
2. Restart after the machine
totally stop or set[E-30]as“2”
;
o.U.2
Dec over
voltage
1.Dec time is too
short;
2. Potential load or
inertia
is
too
big;
;
3. Supply voltage
overrun;
1. Lengthen deceleration time;
2. Decrease potential load, or
amplify the frequency inverter
capacity, or install more
braking unit;
3.Check the network voltage ,
troubleshooting;
o.U.3
Over
voltage
at
constant
speed
1.Supply
voltage
overrun;
2.Input voltage is
abnormal
1.Check the network voltage ,
troubleshooting;
2.Install input reactor;
o.U.4
Close
down over
voltage
1.Supply
voltage
overrun;
1. Check the network voltage,
troubleshooting;
2. Ask for technical support;
Summary of Contents for AC60 series
Page 1: ...Manual AC60 series frequency inverter Version V2 0...
Page 30: ...26...
Page 44: ...40 2 Double display keyboard cycle switch the display of monitoring parameter mode...
Page 46: ...42 2 Double display keyboard parameter setting mode...
Page 162: ...158 8 2 2 Over current...
Page 163: ...159 8 2 3 Over voltage...
Page 164: ...160 8 2 4 Supply voltage is too low...
Page 165: ...161 8 2 5 Inner inverter over heat...
Page 166: ...162 8 2 6 Over load...
Page 167: ...163 8 2 7 No display 8 2 8 Motor heat...
Page 168: ...164 8 2 9 Motor does not rotate...