135
H-14
PID preset
frequency
Range:0.00Hz~frequency
upper limit
Factory setting:
0.00 Hz
H-15
PID preset
frequency operation
time
Range:0.1~6500.0 second
Factory setting:
0.0 second
This function is defined as this: after PID running , frequency inverter
will accelerate to the PID preset frequency [ H-14 ] according to the
acceleration \deceleration time 1 firstly and run for PID preset frequencies
running time [H-15] , then run according to the PID closed-loop
characteristics.