VEGAPULS 56K
69
VEGALOG
VEGAMET
Rx
Set-up
Connection to a VEGA-signal conditioning
instrument
If you operate a sensor suitable for HART
®-
protocols on a VEGA-signal conditioning
instrument, you have to connect the sensor via
a resistor acc. to the following table during the
HART
®
-adjustment, to reach together with the
inner resistor of the instrument the value of
250␣ Ohm required for the HART
®
-instrument.
VEGA-signal conditioning instr.
Rx
VEGAMET 513, 514, 515, 602
50 … 100 Ohm
VEGAMET 614
no additional
VEGADIS 371
resistor
required
VEGAMET 601
200 … 250 Ohm
VEGASEL 643
150 … 200 Ohm
VEGAMET 513 S4, 514 S4
515 S4,
VEGALOG EA-card
100 … 150 Ohm