DSGH Installation and Operation Guide
47
Calibration
Procedure 3.3: To perform a data collection
Calibration
The recommended calibration for a density gauges is a two-point
calibration. The two-point calibration measures the low and high process
conditions.
The two-point calibration method involves three main steps:
1.
Setting the low density
2.
Setting the high density
3.
Calculating the calibration
1 Setting the low density and collecting Cal Low data
You must:
1.
Use the gauge to measure the low process density.
2.
Enter the actual density.
This sets the low end (sometimes called 0) of the calibration curve. Perform
this procedure before or after setting the high density.
1.
Select
Calibrations
|
Data Collect
.
2.
Click
Execute
.
3.
Set the process to a known point.
4.
Click
Start
.
After the data collection, the number of counts output by the
gauge appears.
5.
Click
Accept
.
6.
Repeat as often as necessary if checking repeatability.
Note: The two-point calibration method is useful in conjunction with
any linearizer method.
Summary of Contents for DSGH
Page 2: ......
Page 4: ...2 DSGH Installation and Operation Guide NOTES ...
Page 8: ...6 DSGH Installation and Operation Guide NOTES ...
Page 12: ...10 DSGH Installation and Operation Guide Preface NOTES ...
Page 32: ...30 DSGH Installation and Operation Guide Installation Mounting the DSGH gauge ...
Page 56: ...54 DSGH Installation and Operation Guide Calibration NOTES ...
Page 94: ...92 DSGH Installation and Operation Guide Diagnostics and repair NOTES ...
Page 98: ...96 DSGH Installation and Operation Guide NOTES ...
Page 99: ......