14. SPILLAGE & FLAME SUPERVISION CHECKS
14.1 Check for spillage.
1.
Close all doors and windows in the room containing the appliance.
2.
Light the appliance and turn the control knob to “HIGH”.
3.
Leave the appliance on for five minutes.
4.
Place the smoke match into the appliance
canopy (See figure 37).
5.
The installation is satisfactory if the smoke is
drawn into the appliance. If the smoke is not drawn
into the appliance, leave the appliance alight at the
maximum setting for a further ten minutes and then
repeat the test. If smoke is still not drawn into the
appliance, inspect the sealing to the fireplace
surround. If the sealing is satisfactory but the
appliance is installed with the flue restrictor (See
section 8.2), remove the restrictor, reseal the
appliance and retest. If smoke is still not drawn into
the appliance,
disconnect the appliance and
seek expert advice.
6.
If the above test is satisfactory, open all internal connecting doors, hatches, etc., in
the room. Keep all doors and windows that open to the outside of the building closed.
Recheck for spillage as above. If an extractor fan is installed in the same room as the
appliance or a connecting room, check that spillage does not occur with the fan
operating and all doors and other openings between the fan and the appliance open.
If the smoke is drawn into the appliance, continue with the installation. If the test is
not satisfactory,
disconnect the appliance and advise the customer of the cause
of failure.
14.2 Flame supervision and spillage monitoring system.
The pilot unit incorporates a system that will automatically shut off the gas supply if
the pilot flame goes out or if there is insufficient oxygen due to spillage or lack of
ventilation.
Check that the system operates properly as follows;
1.
Light the appliance. Set the slide control to the maximum burning position and
leave for one minute.
2.
Set the control to the Low burning position. Isolate the gas supply at the inlet ‘T’
connector. The pilot and main burner will go out.
Note the time when the pilot goes
out
.
Listen for a snap sound at the gas tap.
Note the time when the sound is
Page 39
©
Baxi Heating U.K. Limited 2010.
INSTALLER GUIDE
A spillage check must be made before leaving the installed appliance with the
customer. Make this with all the ceramic fuel effect pieces in position
.
Figure 37. Spillage check
Summary of Contents for 954
Page 20: ...Page 20 Baxi Heating U K Limited 2010 INSTALLER GUIDE Figure 7 Pack contents...
Page 21: ...Page 21 Baxi Heating U K Limited 2010 INSTALLER GUIDE Figure 7 Pack contents continued...
Page 22: ...Page 22 Baxi Heating U K Limited 2010 INSTALLER GUIDE Figure 7 Pack contents continued...
Page 64: ...Baxi Heating U K Limited 2010...