8.2 The flue restrictor.
This appliance is supplied with a flue restrictor
for use where the flue draught is excessive.
Generally we recommend the restrictor is NOT
fitted where a precast flue, metal flue box or a
125mm flue liner is used, however, certain
flues may work sufficiently to warrant its use.
There may however, be circumstances where
fitting the restrictor causes the fire to fail the
spillage test. In such cases the restrictor will
have to be removed. After removal conduct
the spillage check again.
The restrictor is packed flat with the appliance
and will require bending prior to fixing. Bend
the restrictor as shown in figure 13.
Fit the restrictor as shown in figure 14 using
the two screws provided.
Page 26
©
Baxi Heating U.K. Limited 2010.
INSTALLER GUIDE
Figure 14. Fixing restrictor
Figure 13. Bending the restrictor
Figure 12. Fitting the foam seal