Operating, installation and maintenance instructions 

For the end user and the competent person

Safety 

1.1 

Action-related warnings

The action-related warnings are classified in accordance
with the severity of the possible danger using the following
warning symbols and signal words:

Warning symbols and signal words

Danger!

Imminent danger to life or risk of severe 
personal injury

Danger!

Risk of death from electric shock

Warning!

Risk of minor personal injury

Caution!

Risk of material or environmental dam-
age

1.2 

Intended use

There is a risk of injury or death to the user or others, or of 
damage to the product and other property in the event of 
improper use or use for which it is not intended.
Photovoltaic modules are designed as stationary power 
generators for photovoltaic installations in combination with 
a suitable inverter.
The photovoltaic modules must never be used for mobile 
operation or a façade installation. It is not permitted to use 
mirrors or lenses to concentrate the sunlight on the surface 
of the module.
Intended use includes the following:
– Observance of all other applicable documents for the 
product and any other system components
– Installing and fitting the product in accordance with the 
product and system approval
– Compliance with the inspection and maintenance condi-
tions.
Intended use also covers installation in accordance with the 
IP code.
Any other use that is not specified in these instructions, or 
use beyond that specified in this document, shall be consid-
ered improper use.
Any direct use in industrial or commercial processes is also 
deemed to be improper.

1.3 

General safety information for the end user 

and competent person

Danger caused by improper operation

Improper operation may present a danger to you and oth-
ers, and cause material damage.

 

>

Carefully read the enclosed instructions and all other 
applicable documents, particularly the „Safety“ section 
and the warnings.

 

>

As the end user, you should only carry out those activi-
ties for which these operating instructions provide 
instructions.

Risk of death from electric shock

Photovoltaic modules can create a high DC voltage at any 
time.

 

>

Keep away from current-carrying components.

Risk of injury and material damage due to mainte-

nance and repairs carried out incorrectly or not 

carried out at all

 

>

Have faults and damage eliminated immediately.

 

>

Adhere to the maintenance intervals specified.

Risk of death caused by missing fall protection

 

>

Secure people and material against falls.

1.4 

General safety information for the 

competent person

Risk caused by inadequate qualifications

All of the work that is described in the installation and main-
tenance instructions must only be carried out by sufficiently 
qualified competent persons.

 

>

Proceed in accordance with current technology.

Risk of death from electric shock

There is a risk of death from electric shock if you touch live 
components.
Before commencing work on the product:

 

>

Disconnect the product from the power supply by switch-
ing off all power supplies at all poles (electrical partition 
with a contact gap of at least 3 mm, e.g. fuse or circuit 
breaker).

 

>

Secure against being switched back on again.

 

>

Check that there is no voltage.

 

>

Ensure that the insulation is not missing or defective. 

When the photovoltaic module is de-energised and earthed, 
this may result in a high voltage.

 

>

Before carrying out any electrical work on the photovol-
taic module, remove the earthing from the photovoltaic 
module.

The photovoltaic modules generate high DC voltages even 
when the light incidence is low.

 

>

Never touch the electrical connections without wearing 
protective gloves.

 

>

When working on the cabling, de-energise the photovol-
taic installation as described in the instructions for the 
inverter.

 

>

Always use a suitable insulated tool.

 

>

Cover the photovoltaic modules with an opaque plastic 
film or a fleece.

If the connections are not established or disconnected prop-
erly, this may lead to an arc forming.

 

>

Avoid working on electrical components when the inci-
dence of solar radiation is high.

Damage to the insulating film on the rear of the photovoltaic 
module may lead to a potentially lethal electric shock, fire or 
severe burns.

 

>

Prevent sharp or pointed objects from coming into con-
tact with the insulating film.

 

>

Ensure that the insulating film is not damaged.

Risk of death due to inadequate load-bearing 

capacity of the roof

A roof may collapse as a result of the additional load of the 
photovoltaic modules.
Additional wind and snow loads may cause the roof to col-
lapse.

 

>

Ensure that a structural engineer has confirmed the roof 
as suitable for installing photovoltaic modules.

 

>

Only install the photovoltaic modules on a roof that has 
adequate load-bearing capacity and a suitable mounting 
frame.

2

0020273012_00

Summary of Contents for VPV P 290/2 M SWF

Page 1: ...SWF 0020273300 VPV P 300 2 M BBF 0020273299 VPV P 305 2 M BWF 0020273298 2 1 4 3 1 6 7 5 8 9 2 3 4 5 VPV P en Operating installation and maintenance instructions es Instrucciones de funcionamiento in...

Page 2: ...not carried out at all Have faults and damage eliminated immediately Adhere to the maintenance intervals specified Risk of death caused by missing fall protection Secure people and material against f...

Page 3: ...n W and measurement accuracy toler ance in VMPP Nominal voltage in V IMPP Nominal current in A VOC No load voltage in V ISC Short circuit current in A max Usyst Maximum system voltage in V STC Standar...

Page 4: ...and soft gloves Do not exert tension or pressure on the connection boxes or the cabling 2 2 Storing the photovoltaic module Always store the photovoltaic module in a dry padded location Always store t...

Page 5: ...tant Performance related cross section 4 mm2 Temperature range 40 C 120 C MC4 plug connections 5 image 2 3 4 Series circuit Wire several photovoltaic modules in series schematic diagram image 4 Avoid...

Page 6: ...ominal output Pnom 290 W 300 W 305 W Voltage at Pmax Umpp 31 3 V 31 2 V 31 4 V Current at Pmax Impp 9 25 A 9 63 A 9 72 A Short circuit current Isc 9 80 A 9 97 A 10 06 A No load voltage Voc 39 3 V 39 4...

Page 7: ...s materiales por la realizaci n incorrecta de los trabajos de mantenimiento y reparaci n o por su omisi n Encargue la eliminaci n inmediata de aver as y da os Respetar los intervalos de mantenimiento...

Page 8: ...dulos fotovoltaicos v ase la portada 3 1 Datos en la placa de caracter sticas Dato Significado VPV P 2 Denominaci n de tipo PMPP Potencia calor fica nominal en W con toleran cia de la clasificaci n en...

Page 9: ...los bordes y las esquinas de las placas de cristal Transporte el m dulo fotovoltaico en posici n vertical El m dulo fotovoltaico debe trasladarse entre dos perso nas sujetando por los laterales largos...

Page 10: ...ecci n contra sobreintensidad requerida 3 3 Requisitos para el cableado Sin plastificante Resistente a los rayos UV Secci n transversal con la potencia adecuada 4 mm2 Rango de temperatura 40 C 120 C C...

Page 11: ...instalaci n el ctrica y para el montaje 9 Datos t cnicos VPV P 290 2 M SWF VPV P 300 2 M BBF VPV P 305 2 M BWF Potencia calor fica nominal Pnenn 290 W 300 W 305 W Tensi n a Pmax Umpp 31 3 V 31 2 V 31...

Page 12: ...out moment Tenez vous distance des composants conducteurs Risques de blessures et de dommages mat riels en cas de maintenance ou de r paration n glig e ou non conforme En pr sence d anomalies de fonct...

Page 13: ...ig neusement cette notice ainsi que tous les autres docu ments compl mentaires applicables pour pouvoir vous y r f rer ult rieurement 3 Description du produit Composition du produit vue d ensemble de...

Page 14: ...pointu ou tranchant 2 4 Contr le du contenu de la livraison Quantit D signation 1 Module photovolta que 1 Lot de documentation 2 5 Contr le du ch ssis de montage V rifiez que le ch ssis de montage a b...

Page 15: ...hotovolta ques comme dans le sch ma illustration 4 vitez le montage en boucle illustration 5 3 5 Exigences relatives l onduleur et la mise la terre Reportez vous la notice d installation de l onduleur...

Page 16: ...p 990 x 1660 x 35 mm 990 x 1660 x 42 mm 990 x 1660 x 42 mm Hauteur du cadre 35 mm 42 mm Poids 19 kg Mat riau du cadre Al Raccordements Bo tier de raccordement 2 illustra tion 2 avec 3 diodes bypass c...

Page 17: ...t fall 1 4 Generelle sikkerhetsanvisninger for installat rer Fare p grunn av utilstrekkelige kvalifikasjoner Alt arbeid som er beskrevet i installasjons og vedlikeholds anvisningen m kun utf res av in...

Page 18: ...n Ser No For identifikasjon VDE kontrolltegn 3 2 Serienummer Serienummeret er angitt p et skilt p siden p produktet og p et skilt ved siden av typeskiltet 1 bilde 1 3 3 CE merkingng CE merkingen dokum...

Page 19: ...komponenter 2 10 Montering av solcellemodulen 2 10 1 V r oppmerksom p klemmeflaten b a 6 a Klemmelengde minst 30 mm b Klemmedybde 3 7 mm S rg for tilstrekkelig stor klemmelengde og klem medybde p sol...

Page 20: ...du utelukkende bruke reservedeler som er god kjent for produktet 6 3 Reparasjoner Ta hele solcelleanlegget midlertidig ut av drift side 18 f r Skift ut defekte komponenter Ikke utf r reparasjoner i k...

Page 21: ...lassifisert for bruksklasse A i henhold til IEC 61730 De elektriske effektdataene finner du i databla det eller p typeskiltet 10 Inspeksjons og vedlikeholdsarbeid oversikt Tabellen nedenfor inneholder...

Page 22: ...a a 22 0020273012_00 1 1 1 3 4 1 2 IP 1 3 1 4 1 5...

Page 23: ...ar 0020273012_00 23 2 2 1 2 2 3 3 1 VPV P 2 PMPP VMPP IMPP VOC ISC max Usyst STC IR IP 67 II class C Control No Ser No VDE 3 2 1 1 CE 3 3 4 5 5 1 23 5 2 5 3 6 6 1 7 8 Country Specifics...

Page 24: ...24 0020273012_00 1 2 2 1 2 2 2 4 1 1 2 5 9 7 8 2 6 A 2 7 A 2 8 24 2 9 2 10 2 10 1 b a 6 7 3 b 30 a 2 10 2 3 3 3 1 6 2 25 i Isc 1 25 Voc 2 8 9 1 2 3 2 3 3 2 4 120 40 2 5 MC4 3 4 4 5 3 5 2 7 2 9...

Page 25: ...Pmax Umpp 9 72 A 9 63 A 9 25 A Pmax Impp 10 06 A 9 97 A 9 80 A Isc 39 6 V 39 4 V 39 3 V Voc 990 x 1660 x 42 mm 990 x 1660 x 42 mm 990 x 1660 x 35 mm x x 42 mm 35 mm 19 kg Al 2 2 2 4 1200 MC4 3 800 2 4...

Page 26: ...00 200 II 430 430 200 200 430 430 b c a 1 2 III 120 120 310 310 3 200 200 3 IV 210 210 140 140 3 200 200 3 a a a 250 40 3 4 V a a a 250 40 3 4 42 mm Product with 42 mm frame Producto con marco de 42 m...

Page 27: ...IV Pressure up to 5400 Pa approx 540 kg m suction up to 2400 Pa approx 240 kg m Nivel de carga IV pre si n hasta 5400 Pa aprox 540 kg m succi n hasta 2400 Pa aprox 240 kg m Niveau de charge IV pressio...

Page 28: ...28 0020273012_00 9...

Page 29: ...nte Pol Industrial Apartado 1 143 C La Granja 26 28108 Alcobendas Madrid Tel fono 9 02116819 Fax 9 16615197 www vaillant es 3 GB United Kingdom Vaillant Ltd Nottingham Road Belper Derbyshire DE56 1JT...

Page 30: ......

Page 31: ......

Page 32: ...3012_00 EGESGBNOTN 032018 Subject to technical modi cations Reservado el derecho a introducir modi caciones t cnicas Sous r serve de modi cations techniques Med forbehold om tekniske endringer 0020273...

Reviews: